Products
Grooved Pipe Fittings
GROOVE STRAIGHT TEE
Groove Equal Tee
A fitting for connecting an equal-size branch in grooved piping.

Unit: mm
| STRAIGHT TEE | ||||||
|---|---|---|---|---|---|---|
| DN | NPS | OD | C | M | S10(kg) | S20(kg) |
| 50 | 2 | 60.5 | 78.5 | 78.5 | 0.79 | 0.98 |
| 65 | 2-1/2 | 76.3 | 85.0 | 85.0 | 1.13 | 1.31 |
| 80 | 3 | 89.1 | 86.0 | 86.0 | 1.30 | 1.71 |
| 100 | 4 | 114.3 | 105.0 | 105.0 | 2.03 | 2.68 |
| 125 | 5 | 139.8 | 124.0 | 124.0 | 3.35 | 4.88 |
| 150 | 6 | 165.2 | 143.0 | 143.0 | 4.65 | 6.77 |
| 200 | 8 | 216.3 | 178.0 | 178.0 | 8.91 | 14.3 |
| 250 | 10 | 267.4 | 216.0 | 216.0 | 13.4 | 21.5 |
| 300 | 12 | 318.5 | 254.0 | 254.0 | 21.0 | 30.1 |
| 350 | 14 | 355.6 | 279.5 | 279.5 | 27.3 | 44.8 |
| 400 | 16 | 406.4 | 305.0 | 305.0 | 31.5 | 53.5 |
| 450 | 18 | 457.2 | 343.0 | 343.0 | 42.7 | 70.0 |
| 500 | 20 | 508.0 | 381.0 | 381.0 | 61.0 | 86.6 |
| 550 | 22 | 558.8 | 419.0 | 419.0 | 74.1 | 126.2 |
| 600 | 24 | 609.6 | 432.0 | 432.0 | 93.9 | 139.4 |
Groove Dimensions and Tolerances

Dimension Basis
- A, B : Reference dimensions for groove location and groove width
- C : Groove diameter after roll grooving
- d : Groove depth
- t : Minimum pipe wall thickness
- Max. Allowable Flare Dia. : Maximum allowable flare diameter at the pipe end after grooving
(1) Roll Grooving Dimensions
Unit : mm
| ROLL GROOVING DIMENSIONS | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|
| Nominal Size | OD | A | B | A·B Tolerance | Groove Dia. C | Groove Depth d | Min. Wall t | Max. Allowable Flare Dia. | ||
| DN | NPS | Dimension | Tolerance | |||||||
| 25 | 1 | 33.4 | 15.9 | 7.1 | ±0.8 | 30.2 | -0.4 | 1.6 | 1.65 | 36.3 |
| 32 | 1-1/4 | 42.2 | 15.9 | 7.1 | ±0.8 | 39.0 | -0.4 | 1.6 | 1.65 | 45.0 |
| 40 | 1-1/2 | 48.3 | 15.9 | 7.1 | ±0.8 | 45.1 | -0.4 | 1.6 | 1.65 | 51.1 |
| 50 | 2 | 60.3 | 15.9 | 8.7 | ±0.8 | 57.2 | -0.4 | 1.6 | 1.65 | 63.0 |
| 65 | 2-1/2 | 73.0 | 15.9 | 8.7 | ±0.8 | 69.1 | -0.5 | 2.0 | 2.11 | 75.7 |
| 80 | 3 | 88.9 | 15.9 | 8.7 | ±0.8 | 84.9 | -0.5 | 2.0 | 2.11 | 91.4 |
| 100 | 4 | 114.3 | 15.9 | 8.7 | ±0.8 | 110.1 | -0.5 | 2.1 | 2.11 | 116.8 |
| 125 | 5 | 141.3 | 15.9 | 8.7 | ±0.8 | 137.0 | -0.5 | 2.1 | 2.77 | 143.8 |
| 150 | 6 | 168.3 | 15.9 | 8.7 | ±0.8 | 164.0 | -0.6 | 2.2 | 2.77 | 170.9 |
| 200 | 8 | 219.1 | 19.0 | 11.9 | ±0.8 | 214.4 | -0.6 | 2.3 | 2.77 | 223.5 |
| 250 | 10 | 273.0 | 19.0 | 11.9 | ±0.8 | 268.3 | -0.7 | 2.4 | 3.40 | 277.4 |
| 300 | 12 | 323.8 | 19.0 | 11.9 | ±0.8 | 318.2 | -0.8 | 2.8 | 3.96 | 328.2 |
| 350 | 14 | 355.6 | 23.8 | 11.9 | ±0.8 | 350.0 | -0.8 | 2.8 | 3.96 | 358.1 |
| 400 | 16 | 406.4 | 23.8 | 11.9 | ±0.8 | 400.8 | -0.8 | 2.8 | 4.19 | 408.9 |
| 450 | 18 | 457.0 | 25.4 | 11.9 | ±0.8 | 451.4 | -0.8 | 2.8 | 4.19 | 461.3 |
| 500 | 20 | 508.0 | 25.4 | 11.9 | ±0.8 | 502.4 | -0.8 | 2.8 | 4.78 | 512.1 |
| 550 | 22 | 559.0 | 25.4 | 12.7 | ±0.8 | 550.2 | -0.8 | 4.4 | 4.78 | 563.9 |
| 600 | 24 | 610.0 | 25.4 | 12.7 | ±0.8 | 601.2 | -0.8 | 4.4 | 5.54 | 614.7 |
(2) Extended Groove Depth for Large Diameter Pipe
Unit : mm
| EXTENDED GROOVE DEPTH (LARGE DIAMETER) | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|
| Nominal Size | OD | A | B | A·B Tolerance | Groove Dia. C | Groove Depth d | Min. Wall t | Max. Allowable Flare Dia. | ||
| DN | NPS | Dimension | Tolerance | |||||||
| 200 | 8 | 219.1 | 19.1 | 11.9 | ±0.8 | 209.0 | -0.64 | 3.7 | 2.8 | 220.7 |
| 250 | 10 | 273.0 | 19.1 | 11.9 | ±0.8 | 260.0 | -0.69 | 3.7 | 3.4 | 271.6 |
| 300 | 12 | 323.8 | 19.1 | 11.9 | ±0.8 | 310.0 | -0.76 | 4.3 | 4.0 | 322.8 |
| 350 | 14 | 355.6 | 23.8 | 11.9 | ±0.8 | 347.0 | -0.76 | 4.3 | 4.0 | 358.1 |
| 400 | 16 | 406.4 | 23.8 | 11.9 | ±0.8 | 397.0 | -0.76 | 4.7 | 4.2 | 408.9 |
※ For DN 200 and above, refer to the roll grooving dimensions of the applicable steel pipe and the project specifications.
Notes
- Before installation, verify that the groove diameter, groove depth, pipe end condition and flare diameter meet the specified requirements.
- Grooving dimensions may vary depending on pipe material, wall thickness, equipment settings and working conditions.
- These values are reference dimensions for catalog use and must be verified against the applicable project criteria before production or installation.